Description
SGS series isolators create galvanic isolation between 0/4-20 mA input and 0/4-20 mA output circuits. Isolator doesn’t need any power supply. 0/4-20 mA current output signal can also be processed into voltage 0/2-10V signal with standard 500Ω load resistance. Quality of isolation depends on breakdown voltage and also capacity between separated circuits.
Specification
| Number of inputs |
3
4
|
| Input type |
current (mA)
|
| Input range |
0/4...20 mA
|
| Number of outputs |
3
4
|
| Output type |
0...20 mA
4...20 mA
|
| Galvanic isolation |
2kV, 100pF
between input and output circuit
|
| Load resistance |
0...1000Ω
|
| Power supply |
current loop
21...28V DC
|
| Protection class |
IP 20
|
| Operating temperature |
-20...+60°C
|
| Mounting |
DIN rail
|
| Case dimensions |
22,5 x 99 x 114,5 mm
|
Files
| Data sheet | |
| Brochure EN | |
| Declaration of conformity |